| Installed lighting overall | 1.3 W/ft2 |
| Space sensible cooling | 20 Btu/h·ft2 |
| Space heating load | 15 Btu/h·ft2 |
| Fan system pressure | 4 in. of water |
| Air circulation rates | 1 cfm/ft2 |
| Electric power (overall) | 4.5 W/ft2 |
| Thermal power (overall) | 30 Btu/h·ft2 |
| Hydronic system head | 70 ft. of water |
| Water chiller (water cooled) | 0.6 kW/ton |
| Chilled water system auxiliaries | 0.15 kW/ton |
| Unitary air-conditioning systems | 1.0 kW/ton |
| Annual electric energy | 15 kWh/ft2·yr |
| Annual thermal energy | 10 Btu/ft2·yr·°F day |